A Model to Predict Total Chlorine Residue in the Cooling Seawater of a Power Plant Using Iodine Colorimetric Method
作者: Jih-Terng WangMing-Hui ChenHung-Jen LeeWen-Been ChangChung-Chi ChenSu-Cheng PaiPei-Jie Meng
刊名: International Journal of Molecular Sciences, 2008, Vol.9 (4), pp.542
来源数据库: Directory of Open Access Journals
关键词: anti-fouling agenttotal residual oxidantpower plantcooling water.
原始语种摘要: A model experiment monitoring the fate of total residue oxidant (TRO) in water at a constant temperature and salinity indicated that it decayed exponentially with time, and with TRO decaying faster in seawater than in distilled water. The reduction of TRO by temperature (°K) was found to fit a curvilinear relationship in distilled water (r2 = 0.997) and a linear relationship in seawater (r2 = 0.996). Based on the decay rate, flow rate, and the length of cooling water flowing through at a given temperature, the TRO level in the cooling water of a power plant could be estimated using the equation developed in this study. This predictive model would provide a benchmark for power plant operators to adjust the addition of chlorine to levels necessary to control bio-fouling of cooling water...
全文获取路径: DOAJ  (合作)
分享到:
来源刊物:
影响因子:2.464 (2012)

×
关键词翻译
关键词翻译
  • relationship 关系
  • seawater 海水
  • constant 常数
  • necessary 必要的
  • adjust 
  • equation 方程
  • given 已知的
  • distilled 蒸馏过的
  • temperature 温度
  • exponentially 按指数规律的