Performance analysis of a ductless personalized ventilation combined with radiant floor cooling system and displacement ventilation
作者: Jiying LiuDaniel Alejandro DalgoShengwei ZhuHui LiLinhua ZhangJelena Srebric
作者单位: 1School of Thermal Engineering, Shandong Jianzhu University
2Department of Mechanical Engineering, University of Maryland
3Key Laboratory of Renewable Energy Utilization Technologies for Buildings, Ministry of Education, Shandong Jianzhu University
刊名: Building Simulation, 2019, Vol.12 (5), pp.905-919
来源数据库: Springer Journal
DOI: 10.1007/s12273-019-0521-9
关键词: Computational fluid dynamics (CFD)Ductless personalized ventilation (DPV)Displacement ventilation (DV)Radiant floor cooling system (RFCS)
英文摘要: Abstract(#br)This study conducted the numerical simulation to evaluate the performance of a ductless personalized ventilation (DPV) combined with radiant floor cooling system (RFCS) and displacement ventilation (DV) system. In the non-DPV cases, DV supplies air at temperature of 16 °C and 20 °C, respectively with a flow rate of 2.4 ACH. In the cases with DPV, DPV supplies personalized air, which is drawn at the height of 0.1 m or 0.2 m above the floor, to the face of a seated occupant at flow rates of 3 L/s, 5 L/s and 7 L/s, respectively. The horizontal distance of 0.3 m is designed between DPV air supply opening and occupant face at the height of 1.2m. For all the cases, the floor cooling temperature is set to 20 °C. The vertical air temperature difference at 1.1 m and 0.1 m (Δ T 1.1−0.1...
全文获取路径: Springer  (合作)
分享到:
来源刊物: