Variation of Steady-State Thermal Characteristics of Transformers with OFWF Cooling in Service
作者: Zoran RadakovicAna Popovic
作者单位: 1Institute for Power Transmission and High-Voltage Technology, University of Stuttgart, Pfaffenwaldring 47, 70569 Stuttgart, Germany.
2Power Comm Belgrade, Belgrade, Serbia and Montenegro.
刊名: Electric Power Components and Systems, 2003, Vol.31 (8), pp.817-829
来源数据库: Taylor & Francis Journal
DOI: 10.1080/15325000390219820
关键词: power transformersthermal modelingOFWF cooling
原始语种摘要: The paper presents the thermal model for top oil temperature calculation in transformers with forced oil and water circulation. The model is completely based on the heat transfer theory. The thermal parameters change in time, due to the sedimentation of substances from the water and the oil to the heat exchanger surfaces. Fouling factors at the water and oil sides can be determined based on measurements. The results of procedure application on the hydro power station block transformer 2 × 190 MVA/380 MVA are given in the paper. The model is aimed at estimation of transformer loading possibilities, but also at maintenance or reconstruction planning purposes.
全文获取路径: Taylor & Francis  (合作)
分享到:
来源刊物:
影响因子:0.62 (2012)

×